CJX2-D50(LC1-D) Magnetic Contactor(NEW)
Product Detailed
Related Categories:Contactors
Detailed Product Description
CJX2-D50(LC1-D) Magnetic Contactor(NEW)(AC Contactor,Electrical Contactor)
Application:
1) It is suitable for using in the circuits up to the rated voltage 660VAC 50Hzor60Hz,rated current 95A,for making and breaking and frequent starting,controlling the AC motor.
2) Combined with the auxiliary contact group,air delayer,machine interlocking device etc.
3) It is combined intothe delay contactor,mechanical interlocking contactor,star-delta starter,with the thermal relay.
4) It is combined into the electromagnetic starter.
Standard control voltage
Voltage | 50Hz | 60Hz | 50/60Hz |
24 | B5 | B6 | B7 |
42 | D5 | D6 | D7 |
48 | E5 | E6 | E7 |
110 | F5 | F6 | F7 |
220 | M5 | M6 | M7 |
230 | P5 | - | P7 |
240 | U5 | U6 | U7 |
380 | Q5 | Q6 | Q7 |
400 | V5 | - | V7 |
415 | N5 | - | N7 |
440 | R5 | R6 | R7 |
500 | S5 | - | - |
660 | Y5 | - | - |
Specification:
Type | CJX2-09 (LC1-D09) | CJX2-12 (LC1-D12) | CJX2-18 (LC1-D18) | CJX2-25 (LC1-D25) | CJX2-32 (LC1-D32) | CJX2-40 (LC1-D40) | CJX2-50 (LC1-D50) | CJX2-65 (LC1-D65) | CJX2-80 (LC1-D80) | CJX2-95 (LC1-D95) | |
Rated working current (A) | AC3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
AC4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |
AC3 capacity of three-phase squirrel-cage motor AC3(kW) | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 |
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |
415V | 4 | 5.5 | 9 | 11 | 15 | 22 | 25 | 37 | 45 | 45 | |
440V | 4 | 5.5 | 9 | 11 | 15 | 22 | 30 | 37 | 45 | 45 | |
500V | 5.5 | 7.5 | 10 | 15 | 18.5 | 22 | 30 | 37 | 55 | 55 | |
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 33 | 37 | 45 | 45 | |
Rated heat current (A) | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | |
Electrical life | AC4X104 | 20 | 20-15 | 20-7 | 15-7 | 15-7 | 10-7 | 7 | 7-6 | 7-5 | 7-5 |
AC3X106 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 1.6 | 1.6 | 1.6 | |
Mechanical lifeX106 | 20 | 20 | 20 | 20 | 20 | 20 | 50 | 20 | 10 | 10 | |
Number of the contact | 3P+NO | ||||||||||
3P+NC | |||||||||||
Matched auxiliary contact type | LA1-DN02(2NC),LA1-DN11(1NO+NC),LA1-DN20(2NO),LA1-DN22(2NO+2NC),LA1-DN40(4NO,LA1-DN04(4NC),LA1-DN13(1NO+3NC),LA1-DN31(3NO+1NC) | ||||||||||
Matched time delay auxiliary contact type | Time delay after power on:LA2-DT0(0.1-3S),LA2-DT2(0.1-30S),LA2-DT4(10-180S),Time delay after power off:LA3-DR0(0.1-3S),LA3-DR2(0.1-30S),LA3-DR4(10-180S) |